SFD Series
Hazardous Areas
Features
- SF style enclosure with extra depth for your PC
- Shelf and hold down straps for PC provided
- NEMA 4X environmental rating
- SlimView Front-Access (SF) Design
- Industrial Flat Panel display
- 15", 17" or 20" Active matrix color TFT
- 250 Nit brightness, 172 Nit viewable through protective screen
- 20" - 1600 x 1200 resolution
- 15" 1024 x 768 resolution
- 17" 1280 x 1024 resolution
- Auto-Syncs to lower resolutions
- On-screen set-up menu/controls
- Protective safety glass over display
- Standard video interface
- Provided with Integrated Industrial Computer
OR
- With Signal Extender for remote PC interface
- Signal Extender mounted inside rear panel
- Copper Extender - Remote PC up to 400' for 15" and 17" displays, 200' for 20" displays
- Fiber Extender Remote PC up to 3000'
- Optional industrial touchscreen
- Integrated industrial membrane keyboard with pointing device - touchmouse or trackball
- Serial touchscreen controller/drivers
- Sloped top design for water run-off
- Curved keyboard front design
- Front access door with compression latches
- Internal, hidden hinges Designed for easy lift-off of front door
- Two Internal blowers provided for continuous air circulation/cooling
- Conduit plates for power/communication connections
- Suitable for direct wall, table top or pedestal mounting
- Internal, multi-outlet surge suppressor wired to terminal strip
- Shipped fully assembled
- Two year warranty
Purge Features
Model # SV-XP (Class I, Division 1, Groups B, C & D)
- Integrated Type X Purge System
- Provides positive pressurization
- Internal pressure switch
- External spark arresting vent with flowswitch
- Automatic rapid air exchange
- 5 Minute quick start-up
- Automatic power shut-down upon pressure loss
- Provisions for remote alarming
- External bulkhead air connection
- Uses inert gas/compressed air
- Minimal air usage - only 7 SCFH
- Power entry via junction box
- NFPA 496 Compliant for Class I, Division 1,
Groups B, C, D
Model # SV-ZP (Class I, Division 2, Groups A, B, C & D)
Check to see if the new Non-Purged Option is suitable for your configuration.
- Integrated Type Z Purge System
- Provides positive pressurization
- Internal pressure switch
- External spark arresting vent
- Manual rapid air exchange
- 5 Minute quick start-up
- Manual power shut-down upon pressure loss
- Provisions for remote alarming
- External bulkhead air connection
- Uses inert gas/compressed air
- Minimal air usage - only 7 SCFH
- Power entry via junction box
- NFPA 496 Compliant for Class I, Division 2, Groups A, B, C, D
|